Some users encounter diesel combustion engine suddenly running overspeed problem when using diesel generator sets. In fact, many reasons can lead to this issue. When you experience this problem, you need to find out the causes and fix it properly.
Typically, the generator overspeed problem may be caused by the following reasons:
The governor is designed to control the fuel to the engine cylinders so as to control the speed of the unit. If the governor malfunctions and cannot perform its function for some reason, the engine will over speed. Failure of the governor’s internal parts may cause failure of the governor. Governor drive failure is the common reason for the over speeding of engine. You can replace the governor and see if that works. Sometimes, overspeed problems can also occur when mechanical engine governing systems are not installed, commissioned and serviced by qualified personnel.
Check your over speed setting on the governor and make sure it is correct. If it's too low, the generator will trip unnecessarily. If the governor response time is slow or if it is not properly calibrated, it may not be able to adjust quickly enough to the sudden decrease in load, causing the generator to overspeed. In addition to the wrong settings of the governor, excess wear in the linkages between the governor and the fuel rack/pump/throttle can also lead to the over speeding issue. You should check governor linkages and make sure they are in good conditions.
The speed signal could be corrupted by an incorrectly mounted or adjusted sensor or system configuration errors, which causes an incorrect input in the system logic. The false signal could affect the control system and lead to an overspeed situation.
In addition to the causes mentioned above, increased throttle due to mechanical or electrical device, increased starting fuel limit, faulty injectors and disturbed setting in control panel can also cause the problem. In most cases, the diesel generator overspeeding appears due to the malfunctioning of the engine governor and fuel injection pumps.
When the generator overspeed occurs, you need to force stop the machine to prevent serious accidents. Measures should be taken to shut down the generator immediately:
Shut off the oil supply system.
For the fuel injection pump with oil supply rod or toothed bar exposed, the rod should be quickly pulled back to the oil stop position.
For the diesel engine with a decompression device, the decompression handle should be quickly pulled to the decompression position, so that the diesel engine will stop due to no compressed gas.
If the closing device is installed in the intake pipe, the fire extinguishing device needs to be stopped immediately.
At present, the control modules of most diesel generator sets feature the function of overspeed shutdown protection. It means that if the control module detects that the engine speed is higher than its set point, the control program will automatically power off to shut down the engine for protection. If your diesel generator doesn’t have this function, it’s recommended that you shut off the engine and troubleshoot problems timely.
Dingbo Power is a professional diesel generator manufacturer with more than 17 years’ experience. We provide high-quality diesel gensets including the brands such as Cummins, Perkins, Volvo, Ricardo, Yuchai, Shangchai, etc. Feel free to contact us with any questions, concerns, or inquiries to learn more about the products & services we provide.