SG (B) 10 series Non-encapsulated H-class Dry-type Power Transformers

Author:firsttransformer 2019-11-30 10:44:22 317 0 0

Dry Type Transformer

Product Description

SG (B) 10 series of non-encapsulated H-class dry-type power transformers adopt the special process technology of German (MORA) dry-type transformers to ensure that the products fully meet the requirements such as fire prevention, waterproof ,environmental protection. It is the ideal product for distribution systems and widely used in the subway, shipbuilding, mining, chemical, power companies and personnel-intensive buildings as well as other special requirements of the occasion for safety.

 

Model and Meaning

SC(B)10 Series Resin-insulated Dry Type Transformer

 

SG (B) 10 series Non-encapsulated H-class Dry-type Power Transformers

Technical Parameter for 6kV, 10kV& 30kVA-2500kVA With Off Circuit Dry Type Transformer

Rated capacityKVA

Voltage Combination

Connection Group Symbol

No-load LossW

Load Loss W

No-load Current (%)

Short-circuit Impedance%

High Voltage (KV)

Tapping ranges of High Voltage

Low Voltage(KV)

130℃(B)(100℃)

155℃(F)(120℃)

180℃(H)(145℃)

30

66.36.61010.511

±2X2.5%±5% 

0.4

Dyn11Yyn0 

190

670

710

760

2.0

4.0

50

270

940

1000

1070

2.0

80

370

1290

1380

1480

1.5

100

400

1480

1570

1690

1.5

125

470

1740

1850

1980

1.3

160

540

2000

2130

2280

1.3

200

±2X2.5%±5%  

620

2370

2530

2710

1.1

250

720

2590

2760

2960

1.1

315

880

3270

3470

3730

1.0

400

980

3750

3990

4280

1.0

500

1150

4590

4880

5230

1.0

630

1340

5530

5880

6290

0.85

630

1300

5610

5960

6400

0.85

6.0

800

1520

6550

6960

7460

0.85

1000

1770

7650

8130

8760

0.85

1250

2090

9100

9690

10300

0.85

1600

2450

11000

11700

12500

0.85

2000

3050

13600

14400

15500

0.70

2500

3600

16100

17100

18400

0.70

1600

2450

1220

12900

13900

0.85

8.0

2000

3050

15000

15900

17100

0.70

2500

3600

17700

18800

20200

0.70

Notes: The load losses listed in the table are the values of the reference temperature for different insulation systems in parentheses; The load losses under other insulation system temperatures that are not included in the table should be according to their respective reference temperatures, the corresponding calculation is based on the"- 155  (F)" insulation system temperature data.

Notes: The Dimension and weight will be changed according to the requirements. These two data in the table will be subject to the factory documents.


Comments   Please sign in or sign up to post.

0

0 of 500 characters used

Copyright:@2020-2021